Difference between revisions of "XFELCooler"

From Atlas Wiki
Jump to navigation Jump to search
Line 28: Line 28:
 
| control valve || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/UKV_PLRCAPBV1A102_KV.pdf Danfoss UKV10D85] [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/Pulse_Converter_Danfoss.pdf Control Unit] || proportional control valve
 
| control valve || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/UKV_PLRCAPBV1A102_KV.pdf Danfoss UKV10D85] [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/Pulse_Converter_Danfoss.pdf Control Unit] || proportional control valve
 
|-
 
|-
| cooling aggregate - Option1 || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/kp-220-4.pdf Bitzer K073H(B)/2GC-2.2Y] ||  
+
/* | cooling aggregate - Option1 || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/kp-220-4.pdf Bitzer K073H(B)/2GC-2.2Y] || */
|-
+
/* |- */
| cooling aggregate - Option2 || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/ECR-010407-offerte-nikhef-1.pdf ECR_Danfoss] || frequency controlled aggregate /  [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/ECR-010407-ALfaLaval-CB27-20H.rtf Condenser sizing]
+
| cooling aggregate || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/ECR-010407-offerte-nikhef-1.pdf ECR_Danfoss] || frequency controlled aggregate /  [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/ECR-010407-ALfaLaval-CB27-20H.rtf Condenser sizing]
 
|-
 
|-
 
| heater || || make sure it is a sealed version
 
| heater || || make sure it is a sealed version

Revision as of 06:44, 8 October 2010

General

Project plan / Specifications

Safety classes for a 90bar pressure vessel

Conceptual Design

XFEL cooler schematics and Controls

Primary circuit test setup

XFEL cooler controls

Calculations

Tube diameters

Accumulator size

Heat Exchanger properties

Components

/* | cooling aggregate - Option1 || Bitzer K073H(B)/2GC-2.2Y || */ /* |- */
component information comment
control valve Danfoss UKV10D85 Control Unit proportional control valve
cooling aggregate ECR_Danfoss frequency controlled aggregate / Condenser sizing
heater make sure it is a sealed version
heat exchanger AXP10 CO2-R404A CO2-CO2 can test to 1.44*Pmax
flow sensor RHM03 NL083183 flow to 1kg/min / different resonance freq. than RHM015 / can provide PED documents
flow transmitter RHE14 together with flow sensor
valve handle extension Valve extender
manual 2-way valve SS-43GHLVCR4 on-off valve with VCR connections / HL option = T form inside ball
manual 3-way valve SS-43GXLVCR4 3-way valve with L pattern
pressure transmitter PTX5072-TC-A2-CA-H0-PE 0-100bar abs GE sensing new product line / can provide conformity document
temperature sensor
pump body Varicon need profibus interface
pump head 1M-J/12/11/X-SS/S/Q/K200/DLC compatible with CO2 / ask for PED documents
relieve valve

Electronics

Drawings