Line 36: Line 36:
 
| heat exchanger || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/PCT00128EN_CBXP27.pdf CBXP27]  [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/AXP10.pdf AXP10]|| can test to 1.44*Pmax / must choose number of plates
 
| heat exchanger || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/PCT00128EN_CBXP27.pdf CBXP27]  [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/AXP10.pdf AXP10]|| can test to 1.44*Pmax / must choose number of plates
 
|-  
 
|-  
| flow sensor || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/RHM_03.pdf RHM03] [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/NL083183_2010_09_03_12_03_34_276-2.pdf NL083183] || flow to 1kg/min / low dP / CHECK RESONANCES! / can provide PED documents
+
| flow sensor || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/RHM_03.pdf RHM03] [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/Rheonik_NL083183_2010_10_06_10_18_05_397-3.pdf NL083183] || flow to 1kg/min / different resonance freq. than RHM015 / can provide PED documents
 
|-
 
|-
 
| flow transmitter || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/RHE_14.pdf RHE14]  || together with flow sensor  
 
| flow transmitter || [http://www.nikhef.nl/pub/experiments/atlas/co2/xfel/Components/RHE_14.pdf RHE14]  || together with flow sensor  

Revision as of 07:37, 7 October 2010

General

Project plan / Specifications

Safety classes for a 90bar pressure vessel

Conceptual Design

XFEL cooler schematics and Controls

Primary circuit test setup

XFEL cooler controls

Calculations

Tube diameters

Accumulator size

Heat Exchanger properties

Components

component information comment
control valve Danfoss UKV10D85 Control Unit proportional control valve
cooling aggregate - Option1 Bitzer K073H(B)/2GC-2.2Y
cooling aggregate - Option2 ECR_Danfoss frequency controlled aggregate / Condenser sizing
heater make sure it is a sealed version
heat exchanger CBXP27 AXP10 can test to 1.44*Pmax / must choose number of plates
flow sensor RHM03 NL083183 flow to 1kg/min / different resonance freq. than RHM015 / can provide PED documents
flow transmitter RHE14 together with flow sensor
valve handle extension Valve extender
manual 2-way valve SS-43GHLVCR4 on-off valve with VCR connections / HL option = T form inside ball
manual 3-way valve SS-43GXLVCR4 3-way valve with L pattern
pressure transmitter PTX5072-TC-A2-CA-H0-PE 0-100bar abs GE sensing new product line / can provide conformity document
temperature sensor
pump body Varicon need profibus interface
pump head 1M-J/12/11/X-SS/S/Q/K200/DLC compatible with CO2 / ask for PED documents
relieve valve